Chiller eddy current testing services for condenser and evaporator tubes

IndustrialImaging matches your chiller tube inspection to eddy current testing companies in your region. Chiller eddy current testing passes a small probe through each condenser or evaporator tube and reports wall loss, pitting and cracking, so you can plug or retube on a plan instead of after a refrigerant leak. Most surveys run while the chiller is open for its regular tube cleaning, which keeps the extra downtime short.

Chiller eddy current testing services for condenser and evaporator tubes
01

What a chiller tube eddy current survey reports

FindingWhat the probe seesWhat you do with it
General wall loss Gradual thinning from erosion or corrosion along the tube Estimate remaining life and plan retubing
Pitting Localized deep defects, often under deposits Plug tubes above your wall loss limit
Support plate wear and fretting Wear where the tube touches the baffle Watch tubes near plates, plug before a through wall failure
Cracks and splits Longitudinal or circumferential indications Plug and review water treatment or vibration
Dents and restrictions Local deformation Check for blockage, note for the next survey

The method works on copper, copper nickel, stainless steel and titanium tubes. Carbon steel tubes need a different technique such as remote field testing. A background article on the method sits on the eddy current testing page, and the wider tube program is covered under heat exchanger inspection services.

02

Who buys chiller eddy current testing

  • Facility and plant engineers who run water cooled chillers on a hospital, campus, data center or manufacturing line and want to know tube condition before a cooling season.
  • Mechanical service contractors that clean tubes every year and want a signed tube report to hand the building owner.
  • Reliability engineers who must decide between plugging, retubing or replacing a 20 year old chiller.
  • Insurers and lenders who ask for a condition report before a large equipment decision.
03

Who this page is for

It fits owners and service companies that need a tube by tube condition report on a water cooled chiller or a shell and tube cooler. It is not for air cooled units with fin coils, where a different probe type applies, and it is not a replacement for a refrigerant leak check. For leak location on sealed systems see helium leak testing services.

04

How a chiller tube inspection runs

  1. The team shuts the chiller down, removes the water box heads and cleans the tubes, because deposits hide defects and block the probe.
  2. The inspector calibrates on a reference tube of the same material and wall thickness.
  3. A probe travels through every tube, or an agreed sample of tubes, and the signals are recorded.
  4. You receive a tube map with each tube marked as good, watch or plug, plus a summary of wall loss by region of the bundle.
  5. Your service company plugs flagged tubes or you plan the retube.
05

What drives the price of a chiller tube survey

  • Tube count. A 300 ton chiller can have several hundred tubes, and most vendors price per tube with a minimum mobilization charge.
  • Access. Remote sites or tight mechanical rooms add setup time.
  • Sample or full. A sample survey of 25 percent costs less, but a full bundle gives a plug list you can act on.
  • Reporting. A tube map with plug recommendations takes longer than a pass or fail list.
  • Timing. Surveys tied to an open chiller for cleaning avoid a second shutdown.

For price ranges per tube and per day, see the cost article on eddy current testing and the broader NDT inspection cost guide.

06

What to put in your chiller eddy current request for quote

RFQ
Draft
  • 01Chiller make, model, tonnage and which bundle (condenser, evaporator or both).
  • 02Tube count, outside diameter, wall thickness and material, including any internally finned tubes.
  • 03Date of last survey and the previous report if you have it.
  • 04Whether tubes will be cleaned and who does it.
  • 05Plugging scope: do you want the inspector to mark tubes only, or does your service company plug them.
  • 06Site location, access limits and the shutdown window.
  • 07Report format, for example a tube map, plug list and wall loss percentages.
07

FAQ

How often should chiller tubes be eddy current tested?

Many owners test every 3 to 5 years on a water cooled chiller with treated water, and more often when the water is aggressive or a prior survey found fast wall loss. Set the interval from the wall loss rate between two surveys. A first baseline survey makes every later comparison useful.

How much does chiller eddy current testing cost?

Price depends on tube count, access and whether the whole bundle or a sample is tested. Vendors usually quote per tube with a minimum charge for mobilization and a report. Send the tube count, material and size in one request so every company quotes the same scope.

Can eddy current testing find a leaking chiller tube?

It finds through wall holes and deep defects that are likely to leak, but it does not measure leak rate. If you are chasing a known leak, test the tubes by eddy current and confirm with a pressure or helium check. A leak test and a condition survey answer different questions.

What is the difference between eddy current and remote field testing for tubes?

Eddy current suits non ferromagnetic tubes such as copper alloys, stainless steel and titanium. Remote field testing handles carbon steel and other ferromagnetic tubes, where eddy current cannot penetrate the wall. The tube material decides the method.

Do I need to clean the tubes before testing?

Yes. Scale and deposits hide defects and can stop the probe, so tubes are cleaned first. Most owners schedule the survey right after the annual tube cleaning, since the heads are already off.

Get matched with eddy current testing companies

Open the inspection method advisor, describe the chiller, the tube material and your location, and it builds a complete request for quote for companies in your region. You compare quotes on one scope instead of explaining the job again to each company.

Inspection request sheet
01What needs inspecting
...
02Material
...
04Concern
...

Run an eddy current testing company? List your company

Show your tube inspection capacity and the states you cover, and receive chiller and heat exchanger requests that fit your work. Learn more for providers.